Contact Information Michael, Chey, General Manager

Address No.303 Taejeon-dong, Gwangju-si, Gyeonggi-do, Korea
464-805

Phone 82-31-764-3093

E-mail c5476687@naver.com

Inquire Now

Taesung Electric Co., Ltd.

Molded Case Circuit Breakers Category : Electronic, Electric, Telecommunication Inquire Now

Molded Case Circuit Breakers image 1
  • Molded Case Circuit Breakers image
  • Product Name : Molded Case Circuit Breakers
  • Brand Name : TAESUNG
  • Model No. :
  • Place of Origin : Korea
  • Main Market : 국가선택,Myanmar,Saudi Arabia
  • Min. Order Quantity : 1000
  • Port : Busan, Korea
  • Certifications : CE,CB,KS,IS9001

[Detailed Product Description]

Structure and Movement(ODP)

1. Arc-extinguish Device
It is designed as a structure that can disperse, cool the arc between contacts to be extinguished efficiently when breaking a large current instantly generated by arc grid arranged in parallel.

2. Full Electronic (ODP) Structure
It is designed as a structure that can disperse, cool the arc between contacts to be extinguished efficiently

3. Checking the movement by handle
  • Trip display
    Incase of auto-breaking due to accidental current such as overcurrent, short-circuit current, handle is stopped at the position in the middle of between ON and OFF.
  • Reset operation
    In case of Trip due to accidental current, remove the cause of accident and reset the handle to OFF by hand and then to ON for normal operation.

4. Improved quality with the durability of product by using special materials

Structure and Movement (Thermal Magnetic)

1. Arc-extinguishing Device
It is designed as a structure that can disperse, cool the arc between contacts to be extinguished efficiently when breaking a large current instantly generrated by arc grid arranged in parallel.

2. Current Limiting Structure
Newly developed current limiting structure sharply decreases and cuts off arc energy without fail.

3. Simultaneous Trip Structure
There is no fear of single-phase running of three-phase motor because three-phase is cut off simultaneously even though electric current flows on any one phase.

A list of types of Molded Case Circuit Breakers(Series for Panel board)

Frame Size
30AF
50AF
Type
for Panel board
for Panel board
Type name
TDB-32
TDB-32a
TDB-32ah
TCB-32bh
TCB-52
TCB-53
External appearance
Rated current(A)
15,20,30
3,5,10,15,20,30,40,50
Rated voltage(Ue) AC(V)
220
220
300
220
460
Number of poles,
Number of elements
2P2E
2P2E
2P2E
2P2E
3P3E
Protective function
Overload and short-circuit protection
Rated
breaking
capacity
(kA)
(sym) AC460V
-
-
-
-
2.5
(sym) AC380V
-
-
-
-
2.5
AC220V
1.5
1.5
2.5
5
5
5
Dim
a
32
33
35
50
75
b
70
70
82.5
96
96
c
36.8
42
60
60
60
d
55
56.5
78
81
81
Product weight(kg)
0.09
0.1
0.48
0.3
0.4
Overcurrent trip type
Thermal magnetic
ODP
Insulating barrier basic
(Power side)
-
-
-
-
Installation method
Screw
Acquired
standards
Electrical Appliances
Safety Certification
O
O
O
O
KSC8321
O
O
O
O

A List of Types of Molded Case Circuit Breakers(Economic Series)

Frame Size
30AF
50AF
Type
for Panel board
for Panel board
Type name
TEB-52
TEB-53
TEB-54
TEB-52
TEB-53
TEB-54
External appearance
Rated current(A)
3,5,10,15,20,30,40,50
30,40,50
Rated voltage(Ue) AC(V)
460
460
460
460
460
460
Number of poles,
Number of elements
2P2E
3P3E
4P3E
2P2E
3P3E
4P3E
Protective function
Overload and short-circuit protection
Rated
breaking
capacity
(kA)
(sym) AC220V
-
5
5
10
10
10
(sym) AC380V
-
5
5
10
10
10
AC220V
10
10
10
22
22
22
Dim
a
50
75
100
50
75
100
b
130
130
130
130
130
130
c
60
60
60
60
60
60
d
80
80
80
80
80
80
Product weight(kg)
0.45
0.65
0.8
0.45
0.65
0.8
Overcurrent trip type
ODP
Insulating barrier basic
(Power side)
O
O
O
O
O
O
Installation method
Screw
Acquired
standards
Electrical Appliances
Safety Certification
O
O
O
O
O
O
KSC8321
O
O
O
O
O
O

[Other Products]